Performance
Characteristics
For airflow
& pressure data please refer to the N.A.T.A. Laboratory Tested Pressure
Drop Data.
Suggested
Specifications
All fire
dampers shall be Kilargo intumescent IFD-LL series, with no moving parts and
allow for bi-directional airflow.
 
Intumescent
fire dampers shall be tested for Fire Resistance Level (FRL) requirements in
accordance with AS 1530.4:2014 Section 10 & Section 11.
Fire Damper
installation shall be strictly in accordance with the relevant requirements of
AS 1682.2, and Kilargo System Installation details including the use of Kilargo
Intumescent Mastic.
 
Features
§  High performance, low-loss design
§  Reduced resistance to air-flow
§  Tested to the latest AS1530.4:2014 Section 10 &
Section 11
§  Insulation up to 120 minutes
§  Wide range of compliant installations
§  Installer label included
§  Ezy-Fit Brackets
§  Wall & floor systems
§  Ultra low-maintenance costs.
 
Technical Data
§  Fire Integrity Rating: 60 / 90 / 120 minutes
§  Insulation Rating: 60 / 90 / 120 minutes
§  Pressure Loss Data – See Curves
§  Sleeve Z275 Galvanised Steel